Range
  1KVA TO 20 KVA (SINGLE PHASE)
  5KVA TO 100 KVA (THREE PHASE)
     
Design
  Modular for easy servicing  
  Tropicallised to suit any working condition  
     
Input
Nominal voltage 165VAC to 265 VAC (SINGLE PHASE)
  330VAC to 460 VAC (THREE PHASE)
Nominal Frequency 45 Hz to 55 Hz  
     
Protection
  Overload / Short circuit  
  Battery Deep Discharge  
  Battery Over Charge  
  Output Under / over Voltage on UPS mode  
     
Output
Output voltage 220 / 230 / 240 Volts (SINGLE pHASE)
  380 / 400 / 415 Volts (THREE pHASE)
  (Optional 110 Volts)  
     
Voltage Regulation +- 1% for input variation and Step Load Change  
  From 10% to 100% +- 2% Typical  
Output Frequency 50 Hz with accuracy < +- 0.1% (Optional 60 Hz)  
Wave Form Sine wave with THD <3%  
Power Factor 0.8 Lagging to Unity  
Type of inverter DSP Controlled Double Update Sine Modulated PWM  
Nominal DC Bus Voltage 192 Volts DC (SINGLE PHASE)
  240/360 Volts DC (THREE PHASE)
Inverter Efficiancy Better than 92%  
Overload 125% for 10 Minutes, 300% for 10 ms  
     
Indications and Metering
LCD Panel Input/Output Voltage ,Input/Output Frequency  
  Battery Voltage, Output Load,  
  Operating Mode (Mains/Battery), Overload/Shortcircuit,  
  Battery Low, Self Diagnostic Check  
  Output Status (On/Off)  
  Battery Low, any overload Audio Alarm  
     
Batteries and Charger
Charger Type IGBT Based Smart Charger  
Backup Time As per requirement  
Type Of Batteries Sealed Maintinance Free, Industrial Tubular  
  Automotive or Nickel-Cadmium  
     
Optional
Software Interface    
RS 232    
Remote Control Inverter On/Off, Output Voltage  
  Output Frequency (At Additional Cost)